Criterion: Emergency Preparedness
Requirements for emergency planning, evacuation drills, and fire safety equipment
Full Description
B2. Emergency Preparedness
Code 8.0
Potential emergency situations and events shall be identified and assessed, and their impact minimized by implementing emergency plans and response procedures including emergency reporting, employee notification and evacuation procedures, worker training, and drills. Emergency drills shall be executed at least annually or as required by local law, whichever is more stringent. Emergency plans shall also include appropriate fire detection and suppression equipment, clear and unobstructed egress, adequate exit facilities, contact information for emergency responders, and recovery plans. Such plans and procedures shall focus on minimizing harm to life, the environment, and property.
Minimum Conformance Requirements
| Core Requirement | Specific Conditions |
|---|---|
| Fire detection, alarm, notification, and suppression systems and equipment are in place, accessible, and fully operational. | Fire alarm: • All buildings have a manual or automatic functioning audible alarm or notification system. • Fire alarm manual call points or pull-stations are provided at or along egress routes to exits. Fire suppression: • Portable fire extinguishers are in place, with unimpeded access and inspection tags. If fire hoses are installed, the same requirement applies. • Fire water tank and pressure are sufficient. |
| Automatic heat or smoke detection and automatic sprinkler systems are installed and fully operational where required by law or insurance. | |
| Fire, heat and smoke detection, alarm, notification, and suppression systems and equipment are inspected, tested, and maintained at required frequencies. | Fire detection: • Single unit fire/smoke detectors are inspected at least once every 6 months. Fire alarm: • The fire alarm control system is free of trouble/supervisory signals. • Fire alarm systems are inspected at the frequency specified by the manufacturer or insurance company. Fire suppression: • Portable fire extinguishers are inspected at least on a monthly basis. |
| Asbestos-containing fire-suppression materials are prohibited. | |
| Emergency, business continuity, business resumption, and post-emergency arrangements are established and kept current as part of an emergency response plan (ERP) for the Entity's identified fire and other emergency risks. | • Incident reporting, investigation and corrective action processes are available and effective. • The ERP is based on risk assessment results. |
| An emergency response team (ERT) is established where required by law or as per the risk assessment, available during all working shifts, and is clearly identifiable. | Emergency responders' roles are clearly identified, and current contact information is accessible during emergencies. |
| Emergency exits, exit access doors, and exit discharge doors are adequate in number and location to enable effective evacuation from all occupied areas and discharge to safe areas. | • Exit discharge doors discharge to safe areas (e.g., open spaces, parking lot) and do not discharge to an enclosed, gated, or locked area. • Emergency exits are inspected and maintained as per the applicable law or the insurance requirements. |
| Means of egress are unobstructed, readily accessible, clearly identified, illuminated, and usable without delay or special effort during an emergency. | • All exit access doors: ◦ can be immediately opened from the inside at all times. ◦ can be opened without a key, badge, code, special knowledge or excessive force ◦ are not equipped with any additional locking arrangement that restricts egress or could be used to restrict egress. ◦ can be opened without reliance on any external triggering to release the door for emergency egress. • Exit access doors that serve indoor areas that are either a. designed for high occupancy (≥ 50 persons), or b. hazardous areas, open in the direction of egress and in a single motion. • All exit discharge doors: ◦ can be immediately opened from the inside at all times, in the direction of egress. ◦ can be opened in a single motion. ◦ do not require a key, badge, code, special knowledge, excessive force, grasping or pinching. ◦ are not equipped with any additional locking arrangement that restricts egress or could be used to restrict egress. ◦ can be opened without reliance on any external triggering to release the door for emergency egress. • Exit discharge doors that serve either a. designed for high occupancy (≥ 50 persons), or b. hazardous areas have a Listed Panic Hardware installed. Special Features: • All sliding doors (horizontal) used as exit access doors or exit discharge doors have a manual safety feature that allows the door to swing to a full-open position in the direction of egress. • All rolling doors (vertical) used as exit access doors or exit discharge doors incorporate an egress feature at the door that allows exit in the direction of egress, which can open in a single motion. |
| Exit routes are clearly identified, illuminated, and supported by functional emergency lighting where needed for safe evacuation. | Exit routes: • Exit routes are appropriately separated, and do not share a common exit. • Exit routes are clear of obstructions and free of material storage. Exit signs: • Exit signs are provided to mark exits on every floor • Exit signs are illuminated or lighted in the event of a power failure • Additional exit or directional signs are provided at main passageways/aisles, long corridors, and other locations where the way to the nearest exit is unclear. Emergency lighting: • Emergency lighting is provided and installed to illuminate means of egress in the event of a power failure. • Emergency lighting is functional and provides adequate illumination in stairs, aisles, corridors, ramps, passageways leading to exits, and other areas as required by applicable laws. • Emergency lighting is powered by either battery or backup generator. |
| Exit enclosures and fire-rated separation are maintained to preserve safe egress during an emergency. | • Penetrations are limited to sprinkler pipes, standpipes, electrical services, pipe and duct installation serving the enclosures. • Openings into the enclosures are protected by fire-rated doors or windows. • Fire doors are in good condition, self-closing, or automatic closing upon fire alarm or detection of smoke. • Integrity of exit enclosures is maintained. |
| Safe internal and external muster points are established and maintained. | • Emergency response kits are easily located and accessible near muster points. |
| Emergency evacuation drills are conducted for fire and other identified emergency risks. | Emergency evacuation drills: • Cover all workers and people on site, all work shifts, and all relevant areas and evacuation routes. • Are executed within 1 month after start of operations or a Significant Change, or as required by local law, whichever is more stringent. • Are conducted at least annually, or as determined by applicable law or risk assessment, whichever is stricter. • Include scenarios representative of identified risks. • Are evaluated for gaps and follow-up action. |
Serious conditions that would be considered as priority risk as per the RBA Code
- Not having firefighting equipment available
- Not having sprinkler or automatic detection systems when they are required by law or insurance.
- Not having alarm and notification system in place.
- The fire alarm control system disengaged, not functioning properly.
- Having firefighting equipment, automatic Detection System or alarm or notification systems are in place, however their function or effectiveness is diminished in such a way that there would be an immediate risk to life during an emergency.
- Not having a comprehensive and up to date Emergency Response Plan (ERP).
- Any emergency support facilities present or poor operating condition such that their function or effectiveness is diminished.
- Emergency exit that is blocked, has restricted egress, or is lacking easy means of egress, posing an immediate risk to life during an emergency.
- No emergency evacuation drill has been held in the last 2 years or within 1 month after the start of operations of the site or a Significant Change.
Additional Guidance
- Processes & Practices are in place such that:
a. Ensure that there is proper budget and staffing allocated to install and maintain the exit, detection, alarm, detection, response, and suppression systems as well as training of individuals and coordination with local authorities.
b. Suggested practice for fire suppression equipment:
- Foam suppression may be used in solvent rooms, data centers or similar spaces.
- Electrically non-conducting portable fire extinguishers (i.e. agent FE-36 or similar permissible) may be used in spaces with electronics.
- Dry powder extinguishers need to be in "Green zone".
- CO2 typically in clean rooms would be weighed.
c. Fire inspection tags on portable fire extinguishers: If portable fire extinguishers do not have inspection tags on them, there is a robust identification system in place that supports the maintenance and safety of the extinguishers.
d. Entity staff or consultants have performed an assessment of potential emergency situations.
e. Emergency Preparedness
- i. Emergency response plans have been developed and implemented to address the potential emergency events identified in the assessment (e.g., chemical spill, equipment malfunction, occupational injury, fire, earthquake, weather event, violence)
- ii. The Entity has implemented emergency reporting procedures, including training for workers on how to report an emergency.
- iii. The Entity maintains alarms and/or a public address system to notify workers of an emergency.
- iv. The Entity has implemented evacuation and relocation processes, and they are tested on a regular basis.
- v. Workers are trained in emergency reporting, notification and evacuation and relocation.
f. Emergency evacuation drills are conducted regularly for all work areas and shifts. Specifically:
- i. Fire evacuation drills2
- All workers (direct/indirect) were part of an evacuation drill.
- All work shifts were part of an evacuation drill.
- At least one evacuation drill is conducted while it is dark outside (this helps to identify access, lighting, and other gaps).
- Drills should include every area (including dormitory, cafeteria, warehouse, office areas, production floors, research, development laboratories, shipping/receiving)
- ii. Other identified emergency evacuations: scope, frequency and process should be determined through risk assessment, local law, or customer requirement.
NOTE: When there is a large turnover in staff, heavy growth and/or significant changes to operations (e.g., new building, equipment/warehouse layout change) a new drill should be conducted.
- i. Fire evacuation drills2
g. Efforts are made to reduce risk such as
- i. Combustible storage is minimized and limited to areas with adequate fire detection and protection.
- ii. Flammable and combustible materials are properly stored to prevent the accumulation of vapors. Ignition hazards (e.g., smoking, electrical sparks, open flames, ...) are eliminated in areas where combustible and flammable materials are stored or used or if there is a flammable atmosphere.
h. When considering emergency egress, an indoor hazardous area can be understood as an area that contains materials, processes, or conditions that could harm occupants during an emergency. Examples include:
- i. Indoor areas that contain toxic substances or contents that are likely to burn with extreme rapidity or explode
- ii. Indoor areas with the potential for a hazardous atmosphere, such as:
- Flammable gas, vapor, or mist in concentrations above 10% of its lower flammable limit;
- Airborne concentration of combustible dust at or above its lower flammable limit;
- Oxygen concentration below 19.5% or above 23.5%.
2 Fire evacuation frequency is at least every 365 days not "1 time per year."
Examples of Emergency Exits – Exit Access and Exit Discharge Doors:
Below are examples Entities can refer to in terms of understanding the RBA Code requirements on emergency exits. Please note that these examples are not prescriptive and not exhaustive:
a. Exit discharge doors, and exit access doors if the door serves indoor areas that are either a. designed for high occupancy (≥ 50 persons), or b. hazardous areas, that comply with the RBA's definition of single motion:
[Photos: a double exit door and a single exit door, each fitted with a horizontal push bar, and a close-up of a vertical push-pad release on a door.]
b. Exit access or exit discharge doors using "grasping or pinching". These types of doors are not appropriate to be used as exit discharge doors, or as exit access doors if the door serves indoor areas that are either a. designed for high occupancy (≥ 50 persons), or b. hazardous areas:
[Photos: a door with a "PULL" grab handle, a hand turning a round doorknob, a door with a round knob, and a lever handle with a lock.]
c. Sliding doors with a safety feature that allows the door to swing to a full-open position in the direction of egress:
[Photos: two automatic sliding glass entrances whose door leaves are swung fully open outward in the direction of egress.]
d. Rolling doors with an egress feature at the door that allows exit in the direction of egress, which can open in a single motion:
[Photos: a metal roller shutter door with an integrated pedestrian exit door, and a high-speed roll-up door with emergency exit panels.]
Controls & Monitoring include:
a. Inspections, maintenance, testing and replacement to the stricter or local law, insurance, or the following:
NOTE: Portable fire extinguishers are inspected at least monthly, single-unit smoke/fire detectors are inspected and tested at least every 6 months.
- i. All other fire safety equipment, the frequency is not be less than that required/recommended by the manufacturer or insurance company, whichever is more stringent.
- ii. All facilities to identify gaps, risks which might lead to an emergency and/or impede the ability to respond and/or evacuate efficiently and safely.
b. Periodically select and follow egress routes out of the building to the assembly/shelter point to confirm conformance.
c. Documenting of evacuation drills followed by analysis and reporting to management on results and plans for improvement.
Records are maintained including:
- a. Business continuity and business resumption plans are available, current, and adequate.
- b. The emergency response plan (ERP) is available, current, adequate, and reflects the risk assessment, including contact information for emergency responders.
- c. A post-emergency plan is available, current, and adequate, which includes incident reporting, root cause investigation, and corrective/preventative actions.
- d. Inspection, maintenance, test and replacement records of equipment and infrastructure including but not limited to fire extinguishers, smoke/fire detectors, alarm, sprinklers, exits
- e. Evaluation drill plans and then reports of the drills including date, time began/ended, shift, area, metrics (e.g., time to evacuate), gaps, Corrective Action Plan that is tracked and reported to completion.
Health and Safety Checklists
Note: These checklists are NOT assessment criteria. These are support tools for an Entity to guide their implementation of an appropriate system towards conformance to the RBA Code of Conduct.
- Each checklist addresses different aspects of health and safety, and each aspect is addressed under its own title and set of questions.
- For each question, three options to answer are available: Y (Yes), N (No) and N/A (Not Applicable), followed by the option to add comments.
B2 Emergency preparedness – Fire Detection, Alarm and Suppression Checklist
Adequate and effective fire detection, alarm and suppression systems are in place.
Detection:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Automatic heat and/or smoke detection is installed as required by insurance company or local law. | ||||
| b | Detector devices and system are in function which give relevant staff notice and allows time to evacuate. |
Alarm:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | All buildings have a manual or automatic fire alarm and notification system to notify people that there is an emergency in the Entity using audible and visual notifications. | ||||
| b | Fire alarm control system is free of trouble/supervisory signals. (Trouble/supervisory signals are usually indicated by orange LED lights; Yellow lights may mean a trouble or supervisory notification in the panel; Red is something in alarm or where an alarm has been silenced rather than reset). | ||||
| c | Fire alarm manual call-points or pull-stations are provided at or along egress routes to exits. |
Fire suppression:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Portable fire extinguishers | ||||
| • Installed, present, visible, and accessible. | |||||
| • In their designated locations, fully charged and free of signs of tampering. | |||||
| • Have a defined distance to place them based upon extinguisher type, size, and use. | |||||
| • Inspected and fire extinguisher inspection tags are present. (Inspection record may be at the extinguisher or if the unit has a bar code / ID, then look at central records.) | |||||
| b | Automatic fire sprinklers | ||||
| • Installed as required by insurance company or local law. | |||||
| • Clear space (based on law / insurance company requirement, or at least 36" if there is no law / insurance company requirement) is maintained under sprinkler head in manufacturing and warehouse spaces, with nothing hanging from it. | |||||
| • Large ducts or objects (based on law / insurance company requirement, or > 48" in a single dimension if there is no law / insurance company requirement) does not obstruct sprinkler heads. | |||||
| • Valves are locked in their normal position (open or closed). Normally open sprinkler control valves are locked in the fully open position. There should be process during work/construction for ensuring properly off or on (e.g. hot work) and after ensuring the sprinklers are back on. | |||||
| • Fire pumps are set to run automatically. | |||||
| c | Fire hose inspection tags are present that indicate they have been inspected. (Inspection record may be at the hose/valves etc. or if the unit has a bar code / ID, then look at central record) | ||||
| d | Fire water tank and water pressure are normal. | ||||
| e | Asbestos-containing fire-suppression materials—for example, blankets—are prohibited. |
Process
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Automatic fire sprinklers (if required by law or insurance company), portable fire extinguishers, heat, and smoke detection (if required by law or insurance company), and an alarm and notification system are inspected, tested, and maintained for good state of operation on a regular basis, as required by insurance company or common practice. |
Records:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Inspection for portable fire extinguishers | ||||
| • Inspection frequency is not less than monthly to check if they are present, visible, and accessible | |||||
| • A schedule for inspections, testing and maintenance is present and there must be verification that it is followed. It should be immediately available. | |||||
| b | Inspection frequency for single unit smoke detectors is not less than every six (6) months. | ||||
| c | All other fire safety equipment | ||||
| • Inspection, testing, and maintenance frequency is not less than that required/recommended by the manufacturer, local code or insurance company whichever is more stringent. | |||||
| • A schedule for inspections, testing and maintenance is present and there must be verification that it is followed. It should be immediately available. | |||||
| • The inspection, testing and maintenance procedure, frequency and results are documented |
B2 Emergency Preparedness – Fire Exits Checklist
Effective emergency exit access, exits, and exit discharge are adequate in number and location, readily accessible, and properly maintained. Clear and unobstructed egress (i.e. Exit access, exit, and exit discharge):
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Exit routes: | ||||
| • Adequate in number from every area and effective. | |||||
| • Separated by an appropriate distance and do not share a common exit. | |||||
| • Clear of obstructions | |||||
| b | Exit discharges: | ||||
| • Discharge to open space/parking lot, and do NOT discharge to an enclosed/gated/locked area | |||||
| • Open out to the public way and do not exit into a courtyard, tank farm, etc. | |||||
| • All exit discharge doors have listed panic hardware installed or able to be pushed open in a single motion. | |||||
| c | Exits | ||||
| • Are free of material storage; and enclosures are not used for any other purpose except for egress | |||||
| • If an exit has a dual use (e.g. moving materials), a process is present to ensure the goods going through are not hazardous and the exit is not obstructed. | |||||
| • Evacuation maps show locations of exit routes, exits, and exit discharges, and are consistent with their actual locations. | |||||
| d | Exit access doors and exit discharge doors | ||||
| • Open in the direction of fire egress if they serve high occupancy (>50) or hazardous areas (include chemical and electrical room) | |||||
| • Are sufficient in number (based on law requirement; if there is no law requirement, it is suggested to have at least 2 exits for >50 occupants, and more exits required for higher number of occupancy) | |||||
| • Are not blocked, and the path is clear. | |||||
| • Open without using a key, badge, code, special knowledge, or effort, and available at all times (i.e. not just during an alarm). | |||||
| • Do not require multiple steps to open. | |||||
| • Do not require a tight grasp to open. | |||||
| • Are not equipped with any additional locking arrangement that restricts egress or could be used to restrict egress. | |||||
| • Can be opened without reliance on any external trigger to release the door for emergency egress. | |||||
| • Are not rolling doors that open vertically, except with an egress feature at/next to it that opens in the direction of egress if the rolling doors have to act as an exit. | |||||
| • Are not sliding doors, except with a safety feature that allows the door to swing full open in the direction of egress. | |||||
| e | Any door labeled as "Exit" follows the requirement of exit access doors / exit discharge doors. |
Exit Signs & Lighting:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Exit signs | ||||
| • Are provided to mark exits on every floor. | |||||
| • Additional exit and/or directional signs (e.g. sign or arrow on the floor) are provided at a regular frequency at main passageways/aisles, long corridors and at other locations where the way to the nearest exit is not clear. | |||||
| • Are not required if a door is not a required exit. | |||||
| • Are illuminated and/or lighted in the event of a power failure | |||||
| Note: There are times when the path is not intuitive, and a door may need labeled "NOT AN EXIT." | |||||
| b | • Emergency lighting | ||||
| • Provided and installed to illuminate means of egress in the event of a power failure. | |||||
| • Provides adequate, functional emergency lighting in stairs, aisles, corridors, ramps, and passageways leading to exits, and in other areas as required by applicable laws. | |||||
| • Generally supposed to have ~1 foot-candle of light along the pathway. | |||||
| • Either battery or backup generator may power emergency lighting. | |||||
| • Random testing of 3 – 4 emergency lights shows that they are functioning. |
Separation:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Penetrations are limited to sprinkler pipes, standpipes, and electrical services, pipe and duct installation serving the enclosures | ||||
| b | Inspection of pipes going through a wall confirm that there is fire-stopping material/putty (typically brick-red in color) are used at through-penetrations and joints, and there are no voids in construction. A process to ensure sealing through-penetrations and joints is included as part of a post construction checklist. | ||||
| c | Openings into the enclosures are protected by fire-rated doors or window. | ||||
| d | Fire doors are in good condition, self-closing, or automatic closing (upon fire alarm or detection of smoke) . | ||||
| e | Random testing of fire doors shows that the latching is functioning. If door is normally closed, then pull open and release / let go and see if it closes and latched by itself. If door is normally held open (e.g. magnetic) then pull it away and see if it closes and latches. | ||||
| f | Inspection procedure / records of fire doors shows that latching is tested regularly. | ||||
| g | The integrity of exit enclosures is maintained. A firewall is usually a masonry wall or distinctly separating unique areas (or through a floor). The Health and Safety person responsible is able to point out which one is the firewall. |
Process:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Adequate and effective process in place to ensure effective emergency exit access, exits and exit discharge with unobstructed egress in place. | ||||
| b | The process includes an assessment of emergency exits after making even minor modifications, tool movements and/or construction in the Entity. |
Records:
| Question | Y | N | N/A | Comments | |
|---|---|---|---|---|---|
| a | Inspection records for emergency support facilities (emergency lighting, emergency exit signs, evacuation paths, exit enclosures, etc.) are maintained showing when / where / how it is done / inspected / maintained / tested / replaced. | ||||
| b | Inspection records for emergency support facilities show that these are inspected as per insurance requirements, or local practice whichever is stricter. | ||||
| c | Review of insurance companies and local authorities visit reports (if applicable, usually visit conducted annually, or if occupancy changed or if building construction / renovation affects over a certain area e.g. >200 ft^2) shows no nonconformance issues |
Profiles using this criterion
RBA Assessment Program
- VAP Full Assessment | 8.1.0
Pass Threshold Metrics
Metric: Evacuation Drill Frequency
Type: Days since last drill
Threshold: 365days (<=) → Conformance
Threshold: 548days (<=) → Minor
Threshold: 730days (<=) → Major
Threshold: 730days (>) → Priority
Metric: Fire Equipment Inspection
Type: Days since inspection
Threshold: 30days (<=) → Conformance
Threshold: 60days (<=) → Minor
Threshold: 90days (<=) → Major
Threshold: 90days (>) → Priority
Conformity Alignment
Priority
Pass: No
Definition: "Critical non-conformance requiring immediate action"
Remediation: 30 days
Major
Pass: No
Definition: "Significant non-conformance requiring corrective action"
Remediation: 90 days
Minor
Pass: Yes
Definition: "Non-conformance with limited impact"
Conditions: Corrective action plan required
Remediation: 180 days
Opportunity
Pass: Yes
Definition: "Opportunity for improvement identified"
Conformance
Pass: Yes
Definition: "Full conformance with criterion requirements"
Related Criterion
VAP: Occupational Health and Safety
Relationship: Related
Fire hazard controls and safety permits
VAP: Food, Sanitation and Housing
Relationship: Related
Dormitory emergency egress requirements
VAP: Health and Safety Management System
Relationship: Parent
Management system for health and safety practices
Change Log
2.0.0 (2026-09-27)
Changed
- Stricter exit-door rules (no external-trigger releases, single-motion/panic hardware); ERT now required in B2: All exit access and discharge doors must open immediately from inside at all times, with no additional locking arrangement and no reliance on an external trigger. This removes the 8.0.x checklist exceptions for delayed-egress panic hardware (15 s), fail-safe REX sensors and electromagnetic door-release buttons. Exit access doors serving high-occupancy (>= 50 persons) or hazardous areas must now open in the direction of egress and in a single motion (8.0.3: direction of egress only). Exit discharge doors must all open in a single motion, and those serving >= 50 persons or hazardous areas must have Listed Panic Hardware (8.0.3: single motion OR panic hardware for any discharge door). New core requirement: an ERT is established where required by law or by the risk assessment, available on all shifts and clearly identifiable, with responder contact information accessible (previously only under B.M.2.1). Emergency drills must cover 'all workers and people on site', include scenarios representative of identified risks, and be held within 1 month of start-up or a Significant Change (previously this appeared only as a priority trigger). The 365-day frequency is unchanged. New conditions: the fire alarm control panel must be free of trouble/supervisory signals, and emergency exits must be inspected and maintained per law or insurance requirements. Rolling (vertical) doors on exit routes, prohibited in 8.0.3, are now allowed if they have a single-motion egress feature. Extinguisher tags may be replaced by a robust ID system. The site policy commitment to meet the stricter of law, RBA, insurance or customer requirements was removed. Priority triggers are unchanged in substance, except that 'throughout the facilities' (alarm) and 'or other' (sprinkler/detection requirement source) were dropped.
1.3.0 (2024-01-01)
Added
- Added numeric severity granularity for drill frequency and fire-equipment inspection: Introduced graduated numeric sub-thresholds for evacuation-drill frequency (<=365d conformance, <=548d minor, <=730d major, >730d priority) and fire-equipment inspection (<=30d conformance, <=60d minor, <=90d major, >90d priority). These fill gradations WITHIN the existing pass envelope (minimum_pass_level=minor) and the >730d (~2yr) priority point matches the prior hard rule 'no drill in last 2 years = Priority'. A facility passing 8.0.0 still passes 8.0.1 — a non-breaking refinement, hence minor. Prose restructured into Policy / Procedures / Controls / Records with no headline rule change. Content is unchanged between VAP 8.0.1 and 8.0.2.
1.2.0 (2023-09-01)
Added
- Drill Priority condition broadened to facilities with no drill since start of operations: The drill Priority text was broadened from 'No emergency evacuation drill held in last 2 years' to 'No emergency evacuation drill has been held in the last 2 years or since the start of operations'. This added clause only affects new facilities with no drills since start of operations; any facility that PASSED 7.1.2 had drills and cannot be newly tripped by it. Fire-system Priority band identical to 7.1.2 ('critically impaired, which poses an immediate risk to life'); a non-breaking addition, hence minor.
1.1.0 (2022-06-01)
Removed
- Fire-system Priority band loosened; graduated drill bands and two standalone criteria removed: Fire-system Priority band loosened from the quantitative '>=10% of firefighting/detection/alarm not functional = Priority' (with '<10% not functional = Major') to the qualitative 'systems are critically impaired which poses an immediate risk to life'; a facility above 10% not-functional but without immediate risk to life is no longer a Priority fail. The graduated drill Major bands (no drill in last year / not all areas, shifts and night drill / post-drill evaluation missing / corrective actions not determined) were dropped in favour of generic finding-severity definitions, retaining only the 2-year Priority threshold. Two standalone audit criteria were removed entirely: old B2.1 (fire-safety permits/licenses) and old B2.6 (emergency-response-team PPE and annual training). All changes are removals or loosenings; no facility passing 7.0.0 can newly fail 7.1.2, hence minor.
1.0.0 (2021-01-01)
Changed
- Initial historical baseline — Emergency Preparedness (RBA Code of Conduct 7.0): Earliest imported version of the criterion. Identification and assessment of potential emergency situations; emergency plans and response procedures covering reporting, notification, evacuation, worker training and drills; fire detection, alarm and suppression equipment; clear unobstructed egress, exit facilities and muster points; recovery plans. Fire-system Priority applied a quantitative band ('>=10% of firefighting/detection/alarm not functional = Priority'; '<10% not functional = Major'). Drill rating used graduated Major bands and a 2-year Priority threshold. Standalone audit criteria covered fire-safety permits/licenses (B2.1) and emergency-response-team PPE and annual training (B2.6).